P40P42A12P1-24 Datasheet PDF - Tyco


www.Datasheet-PDF.com

P40P42A12P1-24
Tyco

Part Number P40P42A12P1-24
Description Definite Purpose Magnetic Contactor
Page 3 Pages

P40P42A12P1-24 datasheet pdf
View PDF for PC
P40P42A12P1-24 pdf
View PDF for Mobile


No Preview Available !

www.DataSheet.co.kr
DC Coil
Catalog 1308242
Issued 3-03 (PDF Rev. 5-05)
P&B
P30/P40 series
AC Coil
Definite Purpose Magnetic Contactor
30/40 Ampere Full Load
40/50 Ampere Resistive
AC & DC Coils
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Features
• AC and DC coils.
• Available with auxiliary switch.
• Variety of main contact terminals.
• For control of motors, power supplies, heating elements and lighting.
Contact Data @ 25°C
Arrangements: Up to 4 Form X (4PST-NO-DM)
Ratings: See contact rating table.
Material: Silver-cadmium oxide.
Expected Life: 200,000 operations at full load.
AC coil: 2 million operations, mechanical.
DC coil: 10 million operations, mechanical.
Minimum Contact Data: 3A @ 120VAC.
Main Contact Ratings
Type
P30
P40
Motor Rating in Amps, 3Ø3P or 1Ø2P
Full Load
Locked Rotor
@ 600V @ 240V @480V @ 600V
30A 180A
150A
120A
40A 240A
200A
160A
Resistive
Rating
@ 600V
40A
50A
Tungsten
Rating
@277V
40A
50A
P30 Electrical Discharge Lamp Control: 40A @ 240V (Delta), 40A @ 600V (Wye).
P40 Electrical Discharge Lamp Control: 50A @ 600V (Wye).
Type
P30
P40
Motor Rating in Horsepower
@ 120V
@ 240V
1Ø2P
3Ø3P
1Ø2P
3Ø3P
1.5HP
3HP
2HP
5HP
3HP
7.5HP
5HP
10HP
@ 440-600V
7.5HP
15HP
Auxiliary Snap-Action Switch
Arrangements: Up to 2 Form C (DPDT).
Rating: 10 amps at 120-250VAC @ 25°C.
Material: Silver.
Initial Dielectric Strength
Initial Breakdown Voltage: 2,200V rms minimum between all elements
and between all elements to ground.
Coil Data @ 25°C
Voltage: From 12 to 120VDC, and 24 to 277VAC, 50/60 Hz.
Power: DC, 7.5 W; AC, 92VA, In rush; 12 VA Sealed.
Duty Cycle: Continuous.
Insulation Class: Class A, standard, Class B available.
Initial Insulation Resistance: 100 megohms, minimum.
Coil Data
Nominal
VDC
12
24
48
120
Resistance
(Ohms ± 10%
@ 25° C)
20.8
84
334
2,110
Must
Operate*
Volts
9
18
36
90
Maximum
Operating
Volts
15
30
57
144
Nominal Coil
Current (ma) @
Nominal Voltage
577
286
144
57
AC Voltage
Rating
24
120
240
277
Nominal
50/60 Hz.
24
110/120
208/240
277
Must Operate*
50/60 Hz.
20.4
94
177
236
*Applicable for vertical mounting, but not for upside-down mounting.
Note: Coil suppression is recommended for all DC coil units, particulary 120 and
240VDC coils.
Operate Data
Must-Operate Voltage: See coil data tables.
Environmental Data
Temperature Range: –55°C to +65°C.
Mechanical Data
Mounting: Universal mounting bracket. See outline drawings.
Termination:
Contacts: Binder screw, box lug, captive pressure plate, combination
screw and dual .250” (6.35mm) quick connect, or
combination box lug and dual .250” (6.35mm) quick
connect. See Main Contact Terminal Options photo.
Coil: Combination 8-32 screw and .250” (6.35mm) quick connect.
Aux. Switch: .187” (4.75mm) quick connect.
Weight: 3 Pole Models: 25 oz. (709g) approximately.
4 Pole Models: 28 oz. (794g) approximately.
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
823
Refer to inside back cover. Datasheetpdf-http://www.DataSheet4U.net/



No Preview Available !

www.DataSheet.co.kr
Ordering Information
Catalog 1308242
Issued 3-03 (PDF Rev. 5-05)
BTypical Part No. P30 P 42 A 1 4
1. Type:
P30 = Definite Purpose Contactor, 30 amp.
P40 = Definite Purpose Contactor, 40 amp.
2. Auxiliary Switch:
P = No Aux. Switch
C = 1 Form C (SPDT)
F = 2 Form C (DPDT)
3. Main Contact Arrangement:
42 = 3 Form X (3PST-NO-DM)
43 = 2 Form X (DPST-NO-DM)
& 1 Form Y (SPST-NC-DB)
45 = 1 Form X (SPST-NO-DB)
& 2 Form Y (DPST-NC-DB)
47 = 4 Form X (4PST-NO-DM)
48 = 2 Form X (DPST-NO-DM)
& 2 Form Y (DPST-NC-DB)
49 = 4 Form Y (4PST-NC-DB)
Other contact arrangements are available.
4. Coil Control Input:
A = Alternating Current, 50/60 Hz.
D = Direct Current
5. Mounting and Installed Accessories:
1 = Standard Mounting
6. Main Contact Terminals:
2 = Screw Terminals
3 = Screw Terminals & Dual .250” (6.35mm) Quick Connect
4 = Box Lug
5 = Captive Pressure Plate
6 = Box Lug & Dual .250” (6.35mm) Quick Connect
7. Auxiliary Contact Terminals:
P = No Auxiliary Switch
C = .187” (4.75mm) Quick Connect
8. Coil Terminals:
1 = Combination 8-32* Screw Terminal and .250” (6.35mm) Quick Connect
9. Coil Voltage:
24, 120, 240 or 277VAC
12, 24 or 120VDC
P
P&B
1 -240
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery.
P30P42A12P1-120
P30P42D12P1-24
P30P47A12P1-120
P30P47D12P1-24
P40P42A12P1-24
P40P42A12P1-120
P40P42A12P1-240
P40P42D12P1-24
Dimensions are shown for
824 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
Datasheet pdf - http://www.DataSheet4U.net/



No Preview Available !

www.DataSheet.co.kr
Outline Dimensions
3 Pole Models
AC Coil
3.25 MAX.
(82.55)
W/SWITCH
2.650 MAX.
(67.31)
W/O SWITCH
Catalog 1308242
Issued 3-03 (PDF Rev. 5-05)
3.420 MAX.
(86.87)
DC Coil
3.975 MAX.
(100.97)
3.800 MAX.
(96.52)
3.550 MAX.
(90.17)
3.550 MAX.
(90.17)
P&B
.21 TYP.
(5.3)
2.550
(64.77)
.25 TYP.
(6.4)
3.125 ± .010
(79.38 ± .25)
.5 DIA.
(12.7)
3.250 ± .010
(82.55 ± .25)
4 Pole Models
AC Coil
3.600 MAX.
(91.44)
W/SWITCH
3.350 MAX.
(85.09)
W/O SWITCH
3.420 MAX.
(86.87)
DC Coil
3.975 MAX.
(100.97)
1.500 ± .020
(38.10 ± .51)
2.00
(50.8)
.21 TYP.
(5.3)
2.550
(64.77)
.25 TYP.
(8.4)
3.550 MAX.
(90.17)
3.800 MAX.
(96.52)
3.550 MAX.
(90.17)
3.125 ± .010
(79.38 ± .25)
.5 DIA.
(12.7)
3.250 ± .010
(82.55 ± .25)
Contact Terminal Options
Code 2
Code 3
Code 4
Code 5
1.500 ± .020
(38.10 ± .51)
2.00
(50.8)
Code 6
#10-32 UNF-2A X .375” (9.525mm)
Binder Terminal Screw 15S365
accepts the following
wire size: Solid, Single — 8 AWG
Dual .250” (6.35mm)
Quick Connect 26A945
#10-32 UNF-2A X .375” (9.525mm)
Binder Terminal Screw 15S365
accepts the following
wire size: Solid, Single — 8 AWG
Box Lug (Keyed) 24C540 with
15S361 & 15S364 Screws
Accepts the following wire sizes:
Solid, Single —14-4 AWG
#10-32 UNF-2A X .500” (12.7mm)
Screw with Captive
Pressure Plate 15S362
Accepts the following wire sizes:
Solid, Single —22-8 AWG
Solid, Double —22-14 AWG
Stranded, Single —22-8 AWG
Stranded, Double —22-16 AWG
Dual .250” (6.35mm)
Quick Connect 26A945
Box Lug 9P30X3
Accepts the following wire sizes:
Solid, Single —14-4 AWG
Main Contact Ordering and Replacement Information
Contact Replacement Kits
Contact replacement kits for 3 pole models include 3 contact pressure springs, 3 movable contact assemblies and 6 stationary contact assemblies. Kits for 4
pole models include 4 contact pressure springs, 4 movable contact assemblies and 8 stationary contact assemblies. Contact replacement kits are for use only
on those models with form X contact arrangements.
Kits for P30 contactors:
3 Form X models - Kit No. 9P30X1
4 Form X models - Kit No. 9P30X2
Kits for P40 contactors:
3 Form X models - Kit No. 9P40X1
4 Form X models - Kit No. 9P40X2
To Replace Contacts:
1. Remove screws holding dust cover in place, and remove cover.
2. Compress and remove contact pressure springs.
3. Lift movable contacts and remove.
4. Remove screws holding stationary contact in place, and remove contacts.
5. Reverse the above procedure to install new stationary and movable contacts.
Caution: Do not overtighten the screws, as it is possible to strip the threads.
Dimensions are shown for
reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
825
Refer to inside back cover. Datasheetpdf-http://www.DataSheet4U.net/




P40P42A12P1-24 datasheet pdf
Download PDF
P40P42A12P1-24 pdf
View PDF for Mobile


Similiar Datasheets : P40P42A12P1-120 P40P42A12P1-24 P40P42A12P1-240

Index :   0   1   2   3   4   5   6   7   8   9   A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z   

This is a individually operated, non profit site. If this site is good enough to show, please introduce this site to others.
Since 2010   ::   HOME   ::   Privacy Policy + Contact