Liquid Level Control Systems
ES825-100F/XF/CF Leak Sensors
Installation Instructions
Sensor Model
ES825-100F
ES825-100XF (Extended Temperature)
ES825-100CF (Chemical Resistant)
Non-Discriminating Leak Sensor
w/Supervised Wiring and
Fault Detection, 24 VDC
For use with the
following consoles:
LC2000
TMS3000
TMS2000
NOTE: ES825-100 SERIES SENSORS ARE NOT COMPATIBLE
WITH Wireless DATA ACQUISITION MODULE (WiDAM) USED
IN CONJUNCTION WITH WIRELESS CONSOLES. REFER TO
THE ES825-300 SERIES.
Bulletin 142 Rev. E (04/09/10)
© COPYRIGHT 2010 PNEUMERCATOR CO., INC.
TEL: (631) 293-8450
FAX: (631) 293-8533
WEBSITE: www.pneumercator.com
PNEUMERCATOR TECHNICAL SUPPORT
1 (800) 209-7858
2/22/2013 12:54:35 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
Page 1 of 4



No Preview Available !

PRODUCT DESCRIPTION: Model ES825-100F is a solid-state, electronic leak sensor utilizing
electo-optic technology to detect the presence of liquids in secondary containment applications. The "X"
version includes all the features of the standard ES825-100F, with operation over an extended temperature
range. The "C" version includes all the features of the standard ES825-100F and the "X" version, with the
addition of a chemical-resistant sensor body and cable compatible with most acids, alkalines and solvents.
The sensors contain no moving parts, are unaffected by vapors, and due to their compact size are ideal for
interstitial spaces. When connected with a LC2000 or TMS series controller, they support Pneumercator's
FAULT-DETECT supervised wiring technology, which automatically detects sensor or field wiring faults.
APPLICATIONS: Sensors can be installed for leak detection in containment, manway and piping sumps,
dry annular space in double-wall tanks, dispenser pans or turbine enclosures. The model selected for each
application depends on its compatibility with the stored product.
SPECIFICATIONS:
MODEL NO. WETTED MATERIALS
ES825-100F *
ES825-100XF *
POLYSULFONE, POLYPROPYLENE,
PVC & EPOXY
POLYSULFONE, POLYPROPYLENE,
PTFE (TEFLON®) & EPOXY
ES825-100CF *
POLYPROPYLENE,
PTFE (TEFLON®) & EPOXY
OPERATING TEMP.
CABLE
-4°F TO +176°F
(-20°C TO +80°C)
22 AWG, 3-CONDUCTOR,
PVC JACKET, 25' LONG
-40°F TO +176°F
(-40°C TO +80°C)
22 AWG, 3-CONDUCTOR,
PTFE (TEFLON®) JACKET,
20' LONG
TECHNOLOGY
ELECTRO-OPTIC,
NO MOVING PARTS
* Approved for UL Class I, Div 1, Groups C and D hazardous locations when used in conjunction with the TMS series controllers.
.62"
(HEX FLAT)
3.00"
CABLE LENGTH
PULL RING REMOVED
3 CONDUCTOR CABLE
PASS-THRU OPENING SIZE
3/4" NPT MINIMUM
REMOVABLE
PULL RING
SHRINK TUBE
("C" & "X" VERSIONS ONLY)
CONVOLUTIONS ACCEPTS 1/2" ENT
1/4" NPT
INSTALLATION: Sensor may be suspended by its cable, placed on the containment or sump floor, or
thru-wall mounted via a 1/4" FNPT opening. Two methods are available when installing in a dry annular space.
The first uses a fish tape and pull string, the second uses a section of 1/2" ENT Flex Conduit attached to the
sensor. Pneumercator recommends that sensor should be installed in an area where there is MINIMAL
exposure to ambient light.
METHOD 1
1. If tank has an existing pull string, skip steps
2 & 5.
2. Insert Fish Tape through annular space.
3. Attach Pull String to sensor.
4. Tag pull string and cable each 16 feet (for
tank diameter up to 10 feet) from sensor.
5. Attach fish tape to pull string.
6. Pull sensor through annulus.
7. Match tag mark on cable and pull string.
8. Sensor now positioned on the bottom
centerline of tank.
METHOD 2
1. Pull sensor cable through Flex Conduit and insert
sensor's back end.
2. Tag conduit at the distance for your tank dia.
3. Feed sensor through annulus.
4. Stop when tag mark is at the top of annulus.
5. Sensor now positioned on the bottom centerline of tank.
TAG MARK
ON CONDUIT
1/2" ENT FLEX
CONDUIT
SENSOR
CABLE
PULL STRING
Bulletin 142 Rev. E (04/09/10)
2/22/2013 12:54:36 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
TAG MARKS:
Ø4" = 75", Ø6" = 115", Ø8" = 150",
Ø10" = 190", Ø12" = 225"
Page 2 of 4



No Preview Available !

WIRING:
! WARNING
Refer to console installation manual for WARNINGS and CAUTIONS before proceeding. FAILURE TO
COMPLY MAY RESULT IN PERSONAL INJURY, PROPERTY LOSS AND EQUIPMENT DAMAGE.
CONSOLE
INTRINSICALLY SAFE
WIRING COMPARTMENT
1" NPT FITTING (TMS3000)
3/4" NPT FITTING (LC2000, TMS2000)
NON-HAZARDOUS
AREA
HAZARDOUS AREA
CLASS I, GROUPS C,D
SECONDARY
CONTAINMENT
AREA
VAPOR SEAL
(AS REQ'D)
SENSOR
CABLE
JUNCTION BOX
(SEE SENSOR WIRING)
SENSOR
CABLE SELECTION:
Use Belden 8443, or Alpha 1173C or any
equivalent 3-conductor, 22 AWG cable, refer
to console installation manual for more cable
selection and limitation information. Shielded
cable is not required, but if used, the shield
wire must be connected to the SENSOR
GROUND TERMINAL in the console I.S.
compartment and should be cut back and left
unterminated at the sensor junction box.
TYPICAL WIRING FOR SENSOR
WIRE SPLICE SEAL CONNECTOR
FOLLOW SUPPLIED WIRE SPLICE INSTRUCTIONS
BULLETIN 180; KIT P/N 10585-3
WATERTIGHT RATED BOX
SUPPLIED BY INSTALLER
TO SENSOR
SENSOR CABLE
CABLE GRIP
REDUCER FITTING
(IF NEEDED)
Bulletin 142 Rev. E (04/09/10)
2/22/2013 12:54:37 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.
CONDUIT AND VAPOR SEAL FITTING
(SIZE AND LOCATION TO BE DETERMINED
BY QUALIFIED INSTALLER)
TO CONSOLE
(AS SHOWN ON NEXT PAGE)
BLK TO BLK
RED TO RED
WHT * TO WHT *
* WHT OR GRN
FIELD CABLE
Note: Shielded cable is not
required, but if used, the shield
wire must be connected to the
SENSOR GROUND TERMINAL
in the console I.S. compartment
and should be cut back and left
unterminated at the sensor
junction box.
Page 3 of 4



No Preview Available !

WIRING CONT'D:
LC2000
RED
WHT OR GRN
BLK
4-PROBE/8-SENSOR
CARD WIRING
TMS2000
+V
+V S
SIG
RED
WHT OR GRN
BLK
NOTE: "S" = SIGNAL AND IS CONSECUTIVELY
NUMBERED "S1" THROUGH "S8" ON THE
TMS2000 CIRCUIT BOARD
TMS3000
16-SENSOR
CARD WIRING
BLK
WHT OR GRN
RED
GND
SIG
+V
RED
WHT OR GRN
BLK
+V
SIG
LC2000/TMSCOMM SOFTWARE PROGRAMMING: Configure the console to activate the
installed sensor(s). Programming is as follows for Models LC2000, TMS2000 and TMS3000.
MAIN
MENU
CONFIG
SUB
MENU
CONTACT
CLOSURE INPUTS
MODEL ES825-100F
ES825-100XF
PGM
ES825-100CF
ITEMS
ENTRY
ISCC ENABLE
SENSOR TYPE
SENSOR MODE
INPUT NAME
ALARM
ES8251
LEAK
THESE PGM
ITEMS FOR
TMS SERIES
ONLY
Select name from list
FAULT DETECTION YES
NORMALLY OPEN
LC2000 FRONT PANEL PROGRAMMING: Configure the LC2000 to activate the installed
sensor(s).
MODEL ES825-100F, ES825-100XF
ES825-100CF
PROGRAM Mode LED Indicators
ENTRY
SENSOR
NO/NC
FAULT DETECT
OFF = DISABLED, ON (2 Fast Blinks) = ALARM, ON (3 Slow Blinks) = RELAY
OFF = NC, ON = NO
OFF = DISABLED, ON = ENABLED
ALARM
ON
ON
TMS SERIES FRONT PANEL PROGRAMMING: Configure the TMS to activate the installed
sensor(s). Programming is as follows for Models TMS2000 and TMS3000.
ACCESS
MAIN
MENU
CONFIG
SUB
MENU
SENSOR INPUTS
MODEL ES825-100F
ES825-100XF
PGM
ES825-100CF
ITEMS
ENTRY
SENSOR ENABLE ALARM
SENSOR TYPE ES8251
SENSOR MODE LEAK
INPUT NAME
Select name from list
FAULT DETECTION YES
Bulletin 142 Rev. E (04/09/10)
NORMALLY OPEN
Page 4 of 4
2/22/2013 12:54:39 PM, 1:1, © COPYRIGHT 2013 PNEUMERCATOR COMPANY, INC.



ES825-100XF datasheet pdf
Download PDF
ES825-100XF pdf
View PDF for Mobile


Related : Start with ES825-100X Part Numbers by
ES825-100XF Leak Sensors ES825-100XF
PNEUMERCATOR
ES825-100XF pdf

Index :   0   1   2   3   4   5   6   7   8   9   A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z   

This is a individually operated, non profit site. If this site is good enough to show, please introduce this site to others.
Since 2010   ::   HOME   ::   Contact