AMEC30-MAZ Datasheet PDF - AIMTEC

www.Datasheet-PDF.com

AMEC30-MAZ
AIMTEC

Part Number AMEC30-MAZ
Description AC-DC / DC-DC Converter
Page 5 Pages


AMEC30-MAZ datasheet pdf
Download PDF
AMEC30-MAZ pdf
View PDF for Mobile


No Preview Available !

Click on Series name for product info on aimtec.com
Series AMEC30-MAZ
30 Watt | AC-DC / DC-DC Converter
Models
Single output
Model
AMEC30-3.3SMAZ
AMEC30-5SMAZ
AMEC30-12SMAZ
AMEC30-15SMAZ
AMEC30-24SMAZ
FEATURES:
4000VAC I/O isolation
Medical Switching power modules for PCB mounting
Operating temperature: -40 to +85°C
Universal Input: 90-260VAC, 47-440Hz, or 130-370VDC
Energy star compliant
RoHS compliant
Low Ripple and Noise
CE, cULus approvals
CB 
Input Voltage
(VAC/Hz)
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
Input Voltage
(VDC)
130-370
130-370
130-370
130-370
130-370
Output Voltage
(V)
3.3
5
12
15
24
Output Current
max
(A)
6
6
2.5
2
1.25
Efficiency
(%)
80
83
85
85
84
Models
Dual output
Model
AMEC30-5DMAZ
AMEC30-12DMAZ
AMEC30-15DMAZ
Input Voltage
(VAC/Hz)
90-264/47-440
90-264/47-440
90-264/47-440
Input Voltage
(VDC)
130-370
130-370
130-370
Output Voltage
(V)
±5
±12
±15
Output Current
max
(A)
±3
±1.25
±1
Efficiency
(%)
81
84
83
AMEC30-24DMAZ
90-264/47-440
130-370
±24 ±0.625
82
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Input Specifications
Parameters
Current
Inrush current <2ms
Leakage current
External fuse
Input dissipation
Start-up time
Conditions
115 VAC
230 VAC
115 VAC
230 VAC
Recommended slow blow type
No load
Typical
3.15
0.5
117
Maximum
740
410
25
50
150
Units
mA
A
µA
A
W
ms
Output Specifications
Parameters
Conditions
Voltage accuracy
Line regulation
(LL-HL)
Load regulation
0-100% load single
0-100% load dual
Cross regulation
25% load - 1st out, 100% load – 2nd out
Maximum Capacitive load
Depending of the model
Transient response deviation
25% load Step
Ripple & Noise*
20MHz bandwidth
Hold-up time (min)
115VAC
Minimum Load Current
*Ripple & Noise measured with 0.1μF M/C and 1μF E/C
Typical
±2
±0.5
±1
±2
±5
470-23 000
±2
50
29
0
Maximum
Units
%
%
%
%
µF
% of Vout
mV p-p
ms
% of Max
www.aimtec.com
F 052e R8.R
Tel: +1 514 620 2722
1 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



No Preview Available !

Isolation Specifications
Parameters
Tested I/O voltage
Isolation Resistance
Conditions
60 sec
Series AMEC30-MAZ
30 Watt | AC-DC / DC-DC Converter
Typical
>1000
Rated
4000
Units
VAC
M
General Specifications
Parameters
Switching frequency
Protection class
Over current protection
Over voltage protection
Short circuit protection
Short Circuit restart
Operating temperature
Maximum case temperature
Storage temperature
Temperature coefficient
Cooling
Humidity
Case material
Weight
Dimensions (L X H X W)
MTBF
Conditions
Typical
Maximum
47
Class II
Auto recovery
110 140
Zener diode clamp
110
Hiccup mode, indefinite
Auto recovery
With derating above 55ºC
-40 - +85
100
-40 to +100
0.02
Free air convection
Non condensing
95
Metal
270
4.92 x 2.56 x 1.38 inch / 125.00 x 65.00 x 35.00 mm
> 800,000 hrs (MIL-HDBK -217F, t=+25 oC)/Full Load
> 200,000 hrs (MIL-HDBK -217F, t=at highest operating temperature)/Full Load
Units
KHz
%
%
oC
oC
oC
% / oC
% RH
g
Environment Approval
Test
Shock
Parameters
Wave form
Acceleration amplitude
Bump duration
Vibration
Converter operation
Number of bumps
Test mode
Displacement
Acceleration
Converter operation
Conditions
Half sine wave
5gn
30 ms
Before and after test, body mounted (on chassis)
18 (3 in each direction for every axis)
Sweep sine, 10-100Hz, speed 0.05Hz/s
1 mm
3g, 3 loops 30min one cycle, 3h total, every axis tested
Before and after test, body mounted (on chassis)
Safety Specifications
Parameters
Agency approvals
cULus, CE, CB
Medical Electrical Equipment
Standards
Information technology Equipment
EMI - Conducted and radiated emission
Harmonic Current Emissions
Voltage fluctuations and flicker
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
RF, Conducted Disturbance Immunity
Power frequency Magnetic Field Immunity
Voltage dips, Short Interruptions Immunity
IEC\EN\UL 60601-1, 2 x MOOP, CSA-C22.2 No. 601.1-
M90
EN 60950-1:2006+A11:2009
EN55011, class B
IEC/EN 61000-3-2, Class A
IEC/EN 61000-3-3, (EN60555-3)
IEC 61000-4-2 Level 3
IEC 61000-4-3 Level 2
IEC 61000-4-4 Level 3
IEC 61000-4-5 Level 2
IEC 61000-4-6 Level 2
IEC 61000-4-8 Level 2
IEC 61000-4-11
www.aimtec.com
F 052e R8.R
Tel: +1 514 620 2722
2 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



No Preview Available !

Pin Out Specifications
Pin Single
Dual
1 AC Input (L) AC Input (L)
2 AC Input (N) AC Input (N)
3 +V Output +V Output
4 -V Output
Common
5 N.C.
Common
6 N.C. -V Output
Dimensions
Series AMEC30-MAZ
30 Watt | AC-DC / DC-DC Converter
www.aimtec.com
F 052e R8.R
Tel: +1 514 620 2722
3 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



No Preview Available !

Optional DIN Rail Bracket
Series AMEC30-MAZ
30 Watt | AC-DC / DC-DC Converter
Derating
www.aimtec.com
F 052e R8.R
Tel: +1 514 620 2722
4 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



AMEC30-MAZ datasheet pdf
Download PDF
AMEC30-MAZ pdf
View PDF for Mobile


Related : Start with AMEC30-MA Part Numbers by
AMEC30-MAZ AC-DC / DC-DC Converter AMEC30-MAZ
AIMTEC
AMEC30-MAZ pdf

Index :   0   1   2   3   4   5   6   7   8   9   A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z   

This is a individually operated, non profit site. If this site is good enough to show, please introduce this site to others.
Since 2010   ::   HOME   ::   Contact