AME15-MAZ Datasheet PDF - AIMTEC

www.Datasheet-PDF.com

AME15-MAZ
AIMTEC

Part Number AME15-MAZ
Description AC-DC Converter
Page 4 Pages


AME15-MAZ datasheet pdf
Download PDF
AME15-MAZ pdf
View PDF for Mobile

No Preview Available !

Click on Series name for product info on aimtec.com
Series AME15-MAZ
15 Watt | AC-DC / DC-DC Converter
FEATURES:
4000VAC I/O Isolation
Operating temperature: -40 to +85°C
Over load, Over Voltage, Short Circuit Protection
Universal input: 90-264VAC, 47-440Hz
RoHS compliant
Soft start
Energy Star compliant
CE, cULus, CB approvals
Models
Single output
Model
AME15-3.3SMAZ
AME15-5SMAZ
AME15-12SMAZ
AME15-15SMAZ
AME15-24SMAZ
Input Voltage Input voltage
(VAC/Hz)
(VDC)
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
130-370
130-370
130-370
130-370
130-370
CB
Output
Voltage (V)
3.3
5
12
15
24
Output Current
Maximum
max (A)
capacitive Load (µF)
3 4700
3 2200
1.25 1000
1 680
0.63 470
Efficiency
(%)
115 230
VAC
VAC
73 73
76 78
78 79
79 82
82 84
Models
Dual output
Model
Input Voltage
(VAC/Hz)
AME15-5DMAZ
AME15-12DMAZ
AME15-15DMAZ
90-264/47-440
90-264/47-440
90-264/47-440
Input voltage
(VDC)
130-370
130-370
130-370
Output
Voltage (V)
±5
±12
±15
Output Current
Maximum
max (A) Capacitive Load (µF)
±1.5
±0.63
±0.5
±1000
±470
±330
Efficiency
(%)
115 230
VAC
VAC
78 79
81 82
82 83
Input Specifications
Parameters
Current
Inrush current <2ms (Cold Start)
Leakage current
External Fuse (recommend)
Input Dissipation
Under Voltage Protection
Start-up time
Conditions
115 VAC
230 VAC
115 VAC
230 VAC
115 VAC
264 VAC
slow blow type
110/230Vac
Typical
2
0.2
85
350
Maximum
350
180
20
30
0.1
0.2
Units
mA
mA
A
A
mA
mA
A
W
VAC
ms
Output Specifications
Parameters
Voltage accuracy
Line regulation
Load regulation (single)
Cross regulation (dual)
Transient Recovery Time
Transient Response Deviation
Ripple & Noise*
Hold-up time
Conditions
LL-HL
0-100%
25% load - 1st out, 100% load – 2nd out
25% load step
3.3 / 5V Models
12 / 15V Models
24V
min
Typical
±2
±1
±1
±5
300
±2
75
100
150
20
* Ripple and Noise are measured at 20MHz bandwidth by using a 0.1μF (M/C) and 47μF (E/C) parallel capacitor
www.aimtec.com
Tel: +1 514 620 2722
F 052e R8.O
1 of 4
Maximum
Units
%
%
%
%
µs
% of Vout
mVp-p
ms
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



No Preview Available !

Isolation Specifications
Parameters
Tested I/O voltage
Isolation resistance
Conditions
60 sec
Series AME15-MAZ
15 Watt | AC-DC / DC-DC Converter
Typical
>1000
Rated
4000
Units
VAC
M
General Specifications
Parameters
Conditions
Typical
Maximum
Units
Switching frequency
132 KHz
Protection class
Class II
Over load protection
Fold Back
130
%
Over voltage protection
Zener diode clamp
Short Circuit protection
Continuous
Short Circuit restart
Auto recovery
Operating temperature
With derating over 55 oC
-40 to +85
oC
Storage temperature
-40 to +100
oC
Max Case temperature
100 oC
Temperature coefficient
±0.02
% / oC
Cooling
Free air convection
Humidity
95 % RH
Weight
100 g
Dimensions (L x W x H)
2.56 x 1.83 x 0.79 inches 65.0 x 46. 5 x 20.1 mm , ±0.5mm
MTBF
> 400,000hrs (MIL-HDBK -217F, t=+25oC)
> 100,000hrs (MIL-HDBK -217F, t=at highest operating temperature)
Case material
Plastic (flammability to UL 94V-0)
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Environment Approval
Parameters
Wave form: Half sine wave
Conditions
Acceleration amplitude: 5gn
Shock
Bump duration: 30 ms
Number of bumps: 18 (3 in each direction for every axis)
Converter operation before and after test, body mounted (on chassis)
Test mode: Sweep sine
10-100Hz, speed 0.05Hz/s
Vibrations
Displacement: 1mm
Acceleration: 3g
3 loops 30min one cycle, 3h total, every axis tested
Converter operation before and after test, body mounted (on chassis)
Safety & EMC Specifications
Parameters
Agency approvals
cULus, CE, CB
Medical Electrical Equipment
Standards
Information technology Equipment
EMI - Conducted and radiated emission
Harmonic Current Emissions
Voltage fluctuations and flicker
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
Electrical Fast Transient/Burst Immunity
Surge Immunity
RF, Conducted Disturbance Immunity
Power frequency Magnetic Field Immunity
Voltage dips, Short Interruptions Immunity
IEC\EN\UL 60601-1, 2 x MOOP,CSA-C22.2 No.
601.1-M90
EN 60950-1:2006+A11:2009
EN55011, class B
IEC/EN 61000-3-2, Class A
IEC/EN 61000-3-3, (EN60555-3)
IEC 61000-4-2 Level 3
IEC 61000-4-3 Level 2
IEC 61000-4-4 Level 3
IEC 61000-4-5 Level 3
IEC 61000-4-6 Level 2
IEC 61000-4-8 Level 2
IEC 61000-4-11
www.aimtec.com
F 052e R8.O
Tel: +1 514 620 2722
2 of 4
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



No Preview Available !

Pin Out Specifications
Pin Single
1 No pin
2 AC Input (N)
3 AC Input (L)
4 -V Output
5 No pin
6 +V Output
Dual
No pin
AC Input (N)
AC Input (L)
-V Output
Common
+V Output
Dimensions (Top View)
Series AME15-MAZ
15 Watt | AC-DC / DC-DC Converter
‐ Case temperature Measurement 
www.aimtec.com
F 052e R8.O
Tel: +1 514 620 2722
3 of 4
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



No Preview Available !

Derating
Series AME15-MAZ
15 Watt | AC-DC / DC-DC Converter
NOTE: 1. Datasheets are updated as needed and as such, specifications are subject to change without notice. Once printed or downloaded, datasheets are no longer
controlled by Aimtec; refer to www.aimtec.com for the most current product specifications. 2. Product labels shown, including safety agency certifications on labels, may vary
based on the date manufactured. 3. Mechanical drawings and specifications are for reference only. 4. All specifications are measured at an ambient temperature of 25°C,
humidity<75%, nominal input voltage and at rated output load unless otherwise specified. 5. Aimtec may not have conducted destructive testing or chemical analysis on all
internal components and chemicals at the time of publishing this document. CAS numbers and other limited information are considered proprietary and may not be available for
release. 6. This product is not designed for use in critical life support systems, equipment used in hazardous environments, nuclear control systems or other such applications
which necessitate specific safety and regulatory standards other the ones listed in this datasheet. 7. Warranty is in accordance with Aimtec’s standard Terms of Sale available at
www.aimtec.com.
www.aimtec.com
F 052e R8.O
Tel: +1 514 620 2722
4 of 4
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only



AME15-MAZ datasheet pdf
Download PDF
AME15-MAZ pdf
View PDF for Mobile


Related : Start with AME15-MA Part Numbers by
AME15-MAZ AC-DC Converter AME15-MAZ
AIMTEC
AME15-MAZ pdf

Index :   0   1   2   3   4   5   6   7   8   9   A   B   C   D   E   F   G   H   I   J   K   L   M   N   O   P   Q   R   S   T   U   V   W   X   Y   Z   

This is a individually operated, non profit site. If this site is good enough to show, please introduce this site to others.
Since 2010   ::   HOME   ::   Contact